1. Scope
The Manual for the rated capacity 10000kVA and below, no excitation regulator and load tap resin dry-type transformer loading and unloading, storage, use and maintenance of voltage class 35kv and below
2. Condition of use
2.1 Normal conditions of use
Meet the following requirements are normal conditions of use conditions of use.
a. Altitude
Not more than 1000m.
b. Ambient temperature
Highest temperature +40℃
Maximum daily average temperature +30℃
Highest annual average temperature +20℃
Minimum temperature -30℃
c. Supply voltage waveform
Supply voltage waveform similar sine wave.
d. Symmetry of multi-phase power supply
Multi-phase transformer is connected to the supply voltage should be approximately symmetrical.
2.2 Special conditions
Article 2.1 of the user's normal use conditions, not including the conditions of use by the Company in consultation with users, and make appropriate adjustments in accordance with relevant standards.
3. Main technology data and standard
3.1 Capacity:10000kVA and 10000kVA and below
3.2 Voltage class:35kV and 35kV and below
3.3 Regulator range:±2×2.5% or others
3.4 Regulator type: None excitation voltage regulator or load tap
3.5 Number of phases: Three-phase or Single-phase
3.6 Frequency:50Hz or 60Hz
3.7 Connection symbol:Dyn11, Yyn0, Yd11 or others
3.8 Cooler type:AN or AF
3.9 Protection class:IP00,IP20 etc.
3.10 Insulation class: F class or H class
3.11 Insulation level:
3.12 Implement standard:GB1094.11-2007、GB/T10228-2008
3.13 Impedance voltage, load loss, load loss, load current, the level of noise and partial discharge level refer to the product test report.