Specifications
Designed for fixed installation indoor and in dry cable conducts. Suitable to be used in application in the area where safety is taken into account by reduce fire, smoke and fume spread in the event of an emergency while limiting electrical interference during operation. The outer screen can be used as a concentric neutral conductor or protective earth.
Construction
Plain copper conductors to IEC60228, XLPE insulation, LSHF bedding, uniform round copper wires wrapped in a helical copper tape, LSHF sheath .
Specification
Rated Voltage: 0.6/1kV
Stranding: Less or equal to 16mm2 solid to IEC 60228 Class 1, Larger or equal to 25mm2 stranded to IEC 60228 Class 2
Bending Radius: 12xOD
Operating Temperature: -30℃ to +70℃ , -5℃ to +70℃ installation
Flame Retardant: IEC 60332-1-2, IEC 60332-3-24
Smoke Emission: IEC 61034-2
Halogen Emission: IEC 60754-2
Standard Manufactured: IEC 60502