Tano Cable Housing Wire Copper Conductor Fire Retardant H05V - R / H05V - U PVC Insulated Electric Wire
Construction of H05V-U Wire
Conductor: annealed copper conductor
class 1 solid -H05V-U
class 2 stranded H05V-R
Insulation: PVC
Color of insulation: blue, black, red, green/yellow or other colors
Standard of H05V-R PVC wire
BS EN 50525-2-31
Application and Description OF CODE NO: THW/TW 600V 10AMG :
The THW conductor is suitable for most current wiring solutions for residential, commercial and industrial environments. It is used in service entrance, feeders and branch circuits for permanent installations. THW conductors in sizes 14 AWG to 1000 Kcmil (MCM) can be installed in conduits and other raceways.
The temperature of installation shall not exceed 75oC(THW), not exceed 90oC(THW2).
Technical Data
Nominal Cross Section Area | Number of wires /Diameter of wires | Approx. Diameter of Conductor | Thickness of Insulation | Approx. Overall Diameter | Approx. Weight of cable | Max. Conductor Resistance at 20°C | Min. Insulation Resistance at 70°C |
mm2 | No./mm | mm | mm | mm | kg/km | Ω/km | MΩ.km |
H05V-U | |||||||
0.5 | 1/0.80 | 0.80 | 0.6 | 2.1 | 8.9 | 36.0 | 0.014 |
0.75 | 1/0.97 | 0.97 | 0.6 | 2.2 | 11.5 | 24.5 | 0.013 |
1 | 1/1.13 | 1.13 | 0.6 | 2.4 | 14.3 | 18.1 | 0.011 |
H05V-R | |||||||
0.5 | 7/0.30 | 0.90 | 0.6 | 2.1 | 8.9 | 36.0 | 0.014 |
0.75 | 7/0.37 | 1.11 | 0.6 | 2.3 | 11.5 | 24.5 | 0.012 |
1 | 7/0.43 | 1.29 | 0.6 | 2.5 | 14.4 | 18.1 | 0.011 |