Tano Cable 300V 500V PVC Insulated Electric H05V - U H05V - R H05V - K Wire Cable
Application
PVC panel wiring for use in the switch control, relay and instrumentation panels of power switchgear and for purposes such as internal connectors in rectifier equipment, motor starters
and controllers.
Standard of H05V - U
BS EN 50525-2-31
Construction of H05V - R
Conductor: annealed copper conductor acc. to EN 60228:
class 1 solid -H05V-U
class 2 stranded H05V-R
class 5 flexible H05V-K
Insulation: PVC compound type TI 1
Color of insulation: blue, black, brown, green/yellow or other colors
Characteristic of H05V - K
Maximum conductor operating temperature: +70°C
Lowest ambient temperature for fixed installation: -30°C
Lowest installation temperature: -5°C
Nominal voltage:Uo/U: 300/ 500 V
Test voltage: 2000V
Minimum bending radius: | For cable diameter D (mm) | |||
D≤8 | 8<D≤12 | 12<D≤20 | D>20 | |
Normal use | 4 D | 5 D | 6 D | 6 D |
Careful bending at termination | 2 D | 3 D | 4 D | 4 D |
Technical Data of H05V-U H05V-R H05V-K
Nominal Cross Section Area | Number of wires /Diameter of wires | Approx. Diameter of Conductor | Thickness of Insulation | Approx. Overall Diameter | Approx. Weight of cable | Max. Conductor Resistance at 20°C | Min. Insulation Resistance at 70°C |
mm2 | No./mm | mm | mm | mm | kg/km | Ω/km | MΩ.km |
H05V-U | |||||||
0.5 | 1/0.80 | 0.80 | 0.6 | 2.1 | 8.9 | 36.0 | 0.014 |
0.75 | 1/0.97 | 0.97 | 0.6 | 2.2 | 11.5 | 24.5 | 0.013 |
1 | 1/1.13 | 1.13 | 0.6 | 2.4 | 14.3 | 18.1 | 0.011 |
H05V-R | |||||||
0.5 | 7/0.30 | 0.90 | 0.6 | 2.1 | 8.9 | 36.0 | 0.014 |
0.75 | 7/0.37 | 1.11 | 0.6 | 2.3 | 11.5 | 24.5 | 0.012 |
1 | 7/0.43 | 1.29 | 0.6 | 2.5 | 14.4 | 18.1 | 0.011 |
H05V-K | |||||||
0.5 | 16/0.20 | 0.91 | 0.6 | 2.2 | 9.2 | 39.0 | 0.013 |
0.75 | 24/0.20 | 1.12 | 0.6 | 2.4 | 12.1 | 26.0 | 0.011 |
1 | 32/0.20 | 1.29 | 0.6 | 2.6 | 14.9 | 19.5 | 0.010 |